Configuring the Environment Sensor
page, Section VII 913-623 @Rev A Environment Sensor
2
Hardware
Installation
Single Sensor
1. Install the ManageUPS Net Adapter P-Series in your UPS.
2. Choose a location to mount the environment sensor within 3m (15’) of your UPS.
3. Use the adhesive-backed
Velcro Strip
to attach the Sensor to the mounting
location.
4. Connect the Blue Bus cable between the Blue Bus port in the ManageUPS Net
Adapter P-Series and a Blue Bus port on the sensor. (Connect the filtered end of
the cable to the ManageUPS Net Adapter P-Series.)
Multiple Sensors
1. Install the first sensor as described above – making
sure to connect the Blue Bus cable from the
ManageUPS Net Adapter P-Series to the IN port on
the first sensor.
2. Connect a Cat5 STP cable between the Blue Bus OUT
port on the first sensor and IN port on the second
sensor.
3. Set the Terminator (switch #1) on the first sensor in
the
DOWN position. Set the terminator in the last sensor
in the
UP position
4. Set the address (switches #2 - #5) of the each
additional sensor to be unique – different from the 1
st
sensor and different from any other sensor on the bus.
Terminator shown in the
UP position.
Address Switch Translation Table
32 = 0000
33 = 0001
34 = 0010
35 = 0011
36 = 0100
37 = 0101
38 = 0110
39 = 0111
40 = 1000
41 = 1001
42 = 1010
43 = 1011
44 = 1100
45 = 1101
46 = 1110
47 = 1111
Address combination
(switches #2-5)
in the “all down”
position is 0000.
This combination will set the value “32” as the
“address” in the CHLORIDE-ENVIRONMENT-
SENSOR.MIB
On the Environment Status web page:
NOTE for Multiple Sensors:
There is a logical limit of 16 addresses
available on the BLUE BUS.
However, the number of sensors that
can be added to the bus without adding
supplemental power is limited by the
power available in the UPS
communications accessory slot.
If you need more sensors than your
UPS can power, add supplemental
power to any sensor on the bus.
Supplemental power will drive that
sensor and any sensors down stream
from the sensor connected to auxiliary
power.
Refer to
Appendix C: Compatibility
Table for ManageUPS Blue Bus
Accessories
to verify the limits for your
UPS.