Summary of Contents

Page 1 - Systems: Site Planning Guide

Stratus TechnologiesR624-01Stratus® ftServer® V 2302, V 4304, and V 6308Systems: Site Planning Guide

Page 2

Prefacex Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)

Page 3 - Contents

Site Planning for ftServer V 2302, V 4304, and V 6308 Systems 1-1Chapter 1Site Planning for ftServer V 2302,V 4304, and V 6308 Systems1-For an overv

Page 4

Site Planning for Fault-Tolerant Systems1-2 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)  Other Infrastructure re

Page 5 - Figures v

Planning for Cables Site Planning for ftServer V 2302, V 4304, and V 6308 Systems 1-3that the system is less fault tolerant, and any I/O throughput d

Page 6

Planning for Cables1-4 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Figure 1-1 illustrates cabling considerations

Page 7 - Notation Conventions

Site Planning Checklist Site Planning for ftServer V 2302, V 4304, and V 6308 Systems 1-5Figure 1-2 illustrates cabling considerations for systems wi

Page 8 - Getting Help

Site Planning Checklist1-6 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) NOTEA dedicated phone line for the RSN mod

Page 9 - Regulatory Notice

Preparing to Install a System Site Planning for ftServer V 2302, V 4304, and V 6308 Systems 1-7❏ Have you created a sketch of how you plan to arrange

Page 10

Preparing to Install a System1-8 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Preparing to Take Delivery of a Syst

Page 11 - V 4304, and V 6308 Systems

System Documentation Site Planning for ftServer V 2302, V 4304, and V 6308 Systems 1-935 in. (89 cm) wide, and all pallets are 41.0 in. (104.2 cm) wi

Page 12

NoticeThe information contained in this document is subject to change without notice.UNLESS EXPRESSLY SET FORTH IN A WRITTEN AGREEMENT SIGNED BY AN A

Page 13 - Planning for Cables

Safety Notices1-10 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Safety NoticesWARNINGWARNING!Risk of explosion if

Page 14

Safety Notices Site Planning for ftServer V 2302, V 4304, and V 6308 Systems 1-11WARNINGWARNING!To prevent fire or current leakage, do not plug the p

Page 15 - Site Planning Checklist

Safety Notices1-12 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) WARNINGWARNING!Do not use or store this product in

Page 16

Safety Notices Site Planning for ftServer V 2302, V 4304, and V 6308 Systems 1-13WARNINGWARNING!Do not disassemble, repair, or alter the server, exce

Page 17 - Preparing to Install a System

Safety Notices1-14 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) WARNINGWARNING!WARNINGWARNING!WARNINGWARNING!WARNI

Page 18 -  Contact the CAC

Safety Notices Site Planning for ftServer V 2302, V 4304, and V 6308 Systems 1-15WARNINGWARNING!|WARNINGWARNING!WARNINGWARNING!

Page 19 - System Documentation

Safety Notices1-16 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) WARNINGWARNING!WARNINGWARNING!WARNINGWARNING!

Page 20 - Safety Notices

AC Power Planning 2-1Chapter 2AC Power Planning2-This chapter describes the AC power requirements of ftServer V 2302, V 4304, and V 6308 systems. It

Page 21

AC Power and HVAC Worksheets2-2 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) The top PDU (or if mounted vertically

Page 22

AC Power and HVAC Worksheets AC Power Planning 2-3For each row in Table 2-1: Fill in the Quantity of Product Purchased column. Multiply it by the s

Page 23

Contents iiiContentsPreface vii1. Site Planning for ftServer V 2302, V 4304, and V 6308 Systems 1-1Site Planning Overview 1-1Site Planning for Fault-

Page 24

Selecting a UPS Unit for ftServer Systems2-4 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Selecting a UPS Unit fo

Page 25 - WARNINGWARNING

Selecting a UPS Unit for ftServer Systems AC Power Planning 2-5Table 2-3. Qualified Chloride UPS Models Region or Country ftServer System Configurati

Page 26

Selecting a UPS Unit for ftServer Systems2-6 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Use Table 2-4 to select

Page 27 - AC Power Planning

Selecting a UPS Unit for ftServer Systems AC Power Planning 2-7Plan for sufficient UPS capacity if you want to connect legacy E124 storage-system cab

Page 28 - AC Power and HVAC Worksheets

Power Cord Summary2-8 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Power Cord SummaryTable 2-6 describes where you

Page 29

Main Cabinet Ground Cables AC Power Planning 2-9Main Cabinet Ground CablesTable 2-7 provides information about the main cabinet ground cable.Table 2-

Page 30

Main Cabinet Ground Cables2-10 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)

Page 31

Space and Component Location Planning 3-1Chapter 3Space and Component LocationPlanning3-This chapter describes the space and location requirements f

Page 32 - UPS model

Fibre Channel Connections3-2 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) For additional information, see the foll

Page 33

UPS Connections Space and Component Location Planning 3-3UPS Connections For management of UPS units, each UPS unit connects to a different U772 Ethe

Page 34 - Power Cord Summary

Contentsiv Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) 4. Other Infrastructure Requirements 4-1Telephone Lines 4-

Page 35 - Main Cabinet Ground Cables

Component Location and Cabling Summary3-4 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) The lengths of supplied cor

Page 36

Room Requirements Space and Component Location Planning 3-5Room RequirementsTo ensure that the installation site provides a properly equipped, cooled

Page 37 - Planning

Room Requirements3-6 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Dust on circuit boards raises the temperature, t

Page 38 - Fibre Channel Connections

Room Requirements Space and Component Location Planning 3-7Figure 3-1. Space-Planning ConsiderationsCabinet Mounting and Leveling ConsiderationsThe m

Page 39 - UPS Connections

Creating a Floor Plan3-8 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Creating a Floor PlanThis section provides e

Page 40

Creating a Floor Plan Space and Component Location Planning 3-9Figure 3-2. System Equipment Templates NOTEThe shading on the templates indicates the

Page 41 - Room Requirements

Creating a Floor Plan3-10 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Figure 3-3. Site-Layout Grid= 1 square foot

Page 42

Other Infrastructure Requirements 4-1Chapter 4Other Infrastructure Requirements4-This chapter desribes other infrastructure requirements, including

Page 43

Network Connections4-2 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)  OpenVOS System Administration: Configuring a

Page 44 - Creating a Floor Plan

Network Connections Other Infrastructure Requirements 4-3Ethernet Subnet RequirementsftServer V 2302, V 4304, and V 6308 systems require separate, cl

Page 45

Figures vFiguresFigure 1-1. Cabling Considerations with RSN Dialup Console Server and Modem 1-4Figure 1-2. Cabling Considerations with RSN Internet Co

Page 46 - = 1 square foot

System PC Console4-4 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) System PC Console You must provide a PC with the

Page 47 - Chapter 4

Supported Configurations 5-1Chapter 5Supported Configurations5-This chapter contains information about supported cabinet configurations.Cabinet Conf

Page 48 - Network Connections

Cabinet Configurations5-2 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Figure 5-1 illustrates an ftServer V 4304 o

Page 49 - Maintenance Network

Cabinet Configurations Supported Configurations 5-3Figure 5-2 illustrates a fully configured ftServer V 4304 or V 6308 system that includes the optio

Page 50 - System PC Console

Cabinet Configurations5-4 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Figure 5-3 illustrates an ftServer V 2302 s

Page 51 - Supported Configurations

System Specifications A-1Appendix ASystem SpecificationsA-For system specifications, see: “System Specifications” on page A-1 “AAP87600V PDU Speci

Page 52 - Cabinet Configurations

System SpecificationsA-2 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Figure A-1. CPU-IO Enclosures: Front ViewFi

Page 53 - I/O enclosure

System Specifications System Specifications A-3Table A-1. Cabinet Dimensions 24U Shipping ContainerHeight (including pallet) 56 in. (1.42m)Width 41

Page 54 - S Y S T E M

System SpecificationsA-4 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Table A-2. V 2302, V 4304, and V 6308 System

Page 55 - System Specifications

System Specifications System Specifications A-5FeaturesProcessors ftServer 2302: One Dual-Core Intel® Xeon® 2.0 GHz processors in each CPU- I Oenclo

Page 56

vi Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) TablesTable 1-1. Ethernet PCI Adapters 1-6Table 1-2. ftServer V 23

Page 57

AAP87600V PDU SpecificationsA-6 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) AAP87600V PDU SpecificationsThe AAP87

Page 58 - C per hour

AAP87600V PDU Specifications System Specifications A-7Table A-3 lists the specifications for the AAP87600V PDUs.Table A-3. AAP87600V PDU: Specificati

Page 59

AAP87600V PDU SpecificationsA-8 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)

Page 60 - AAP87600V PDU Specifications

Electrical Circuit and Wiring Information B-1Appendix BElectrical Circuit and Wiring InformationB-For electrical circuit and wiring information that

Page 61 -  F (1 C)

Circuit Wiring DiagramsB-2 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) As shown in Figure B-1, a star ground is o

Page 62

Circuit Wiring Diagrams Electrical Circuit and Wiring Information B-3(Line) hot input, and the Y input is connected to the N (Neutral) input. However

Page 63 - Appendix B

Circuit Wiring DiagramsB-4 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Figure B-4 shows a single-phase 240V AC ci

Page 64 - Circuit Wiring Diagrams

Circuit Wiring Diagrams Electrical Circuit and Wiring Information B-5Figure B-5 shows a split-phase 120/240V AC circuit connection. Note that this ap

Page 65

Circuit Wiring DiagramsB-6 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Figure B-6 shows a three-phase 208V AC, Y-

Page 66

Circuit Wiring Diagrams Electrical Circuit and Wiring Information B-7Figure B-7 shows a three-phase 380V AC, Y-, or -source circuit connection, whic

Page 67

Preface viiPrefaceThe Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) documents the site requirements and customer res

Page 68

Electrical Power ConnectorsB-8 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624) Electrical Power ConnectorsTable B-1 d

Page 69

Standards Compliance C-1Appendix CStandards ComplianceC-For compliance information, see the following: “Electronic Interference, Immunity, Safety,

Page 70 - Electrical Power Connectors

Electronic Interference, Immunity, Safety, and Noise Level Standards ComplianceC-2 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning

Page 71 - Standards Compliance

Electronic Interference, Immunity, Safety, and Noise Level Standards Compliance Standards Compliance C-3VCCI Note BSMI Note TUV NRTL IEC 60950-1, UL

Page 72

Electronic Interference, Immunity, Safety, and Noise Level Standards ComplianceC-4 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning

Page 73 - BSMI Note

Toxic and Hazardous Substances and Elements Disclosure Standards Compliance C-5Toxic and Hazardous Substances and Elements DisclosureftServer V 2302,

Page 74

Toxic and Hazardous Substances and Elements DisclosureC-6 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)

Page 75 - Standards Compliance C-5

Index-1IndexIndex-AAC power, 2-1cordsspecifications, 2-8UPS, 2-7requirements, 2-3source, 2-1worksheet, 2-2American Power Conversion (APC). See APCanti

Page 76

IndexIndex-2 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)IIEC 60309 connector, B-8installation sitefloor plan, 3-8l

Page 77 - IndexIndex

IndexIndex-3UPS, 2-4, 2-6AC power cords, 2-7APC qualified models, 2-6CPP qualified models, 2-5UPS connections, 3-3Wwiring, electrical, B-1worksheetsAC

Page 78

Prefaceviii Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)Getting HelpIf you have a technical question about ftServer

Page 79

IndexIndex-4 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)

Page 80

PrefacePreface ix By email to [email protected]. If it is possible, please include specific information about the documentation on which you are c